Yes and No, Electric space heaters are permitted following theses guidelines.
605.10 Portable, electric space heaters. Where not prohibited by other paragraphs of this code, portable, electric space heaters shall be permitted to be used in all occupancies other than Group I-2 and in accordance with paragraphs (E)(10)(a)(605.10.1) to (E)(10)(d)(605.10.4) of this rule.
Exception: The use of portable, electric space heaters in which the heating element cannot exceed a temperature of 212°F (100° C) shall be permitted in nonsleeping staff and employee areas in Group I-2 occupancies.
- 605.10.1 Listed and labeled. Only listed and labeled portable, electric space heaters shall be used.
- 605.10.2 Power supply. Portable, electric space heaters shall be plugged directly into an approved receptacle.
- 605.10.3 Extension cords. Portable, electric space heaters shall not be plugged into extension cords.
- 605.10.4 Prohibited areas. Portable, electric space heaters shall not be operated within 3 feet (914 mm) of any combustible materials. Portable, electric space heaters shall be operated only in locations for which they are listed.